AC Power Factor Correction Capacitor Calculator
Estimate capacitive reactive power needed to improve an inductive single-phase load’s displacement power factor.
How the calculation works
Required capacitive reactive power = real_power*(sqrt(1/old_pf**2-1)-sqrt(1/target_pf**2-1)) kvar. Ideal shunt capacitance = real_power*1000*(sqrt(1/old_pf**2-1)-sqrt(1/target_pf**2-1))/(2*pi*frequency*voltage**2)*1e6 µF.
Worked example
Example inputs — Real load power (kW): 1; Existing lagging power factor: 0.8; Target lagging power factor: 1; Single-phase RMS voltage (V): 100; Line frequency (Hz): 50. Expected results — Required capacitive reactive power: 0.75 kvar; Ideal shunt capacitance: 238.7324146 µF.
Assumptions and limits
Idealized circuit arithmetic. Component ratings, tolerances, temperature, transients, isolation and electrical safety require independent checks; this tool does not certify a circuit. Ideal single-phase sinusoidal inductive load. Harmonic resonance, switching transients, discharge provisions and capacitor-bank protection require qualified design.