Current Sense Shunt Voltage & Dissipation Calculator
Estimate shunt voltage and heat loss at nominal and peak currents.
How the calculation works
Nominal sense voltage = current*resistance_mohm mV. Nominal continuous dissipation = current**2*resistance_mohm*.001 W. Peak sense voltage = peak_current*resistance_mohm mV. Peak instantaneous dissipation = peak_current**2*resistance_mohm*.001 W.
Worked example
Example inputs — Shunt resistance (mΩ): 10; Nominal current (A): 5; Peak current for voltage estimate (A): 20. Expected results — Nominal sense voltage: 50 mV; Nominal continuous dissipation: 0.25 W; Peak sense voltage: 200 mV; Peak instantaneous dissipation: 4 W.
Assumptions and limits
Idealized circuit arithmetic. Component ratings, tolerances, temperature, transients, isolation and electrical safety require independent checks; this tool does not certify a circuit. Peak dissipation is instantaneous, not an allowed pulse rating. Kelvin connections, tolerance, temperature coefficient and amplifier common-mode limits require checks.