Single & Balanced Three-Phase AC Power Calculator

Calculate real, reactive and apparent power from RMS voltage, current and displacement power factor.

How the calculation works

Apparent power = voltage*current*(sqrt(3) if phase == "three" else 1) VA. Real power = voltage*current*pf*(sqrt(3) if phase == "three" else 1) W. Reactive power magnitude = voltage*current*sqrt(1-pf**2)*(sqrt(3) if phase == "three" else 1) var.

Worked example

Example inputs — RMS voltage: line-neutral for single phase; line-line for three phase (V): 230; RMS line current (A): 10; Displacement power factor: 0.8; Supply configuration: single. Expected results — Apparent power: 2300 VA; Real power: 1840 W; Reactive power magnitude: 1380 var.

Assumptions and limits

Idealized circuit arithmetic. Component ratings, tolerances, temperature, transients, isolation and electrical safety require independent checks; this tool does not certify a circuit. Sinusoidal voltage/current and a balanced load for the three-phase mode. Does not model harmonic distortion or select wiring and protection.

Reference and further reading

Read the underlying subject reference. Calculith is an independent implementation; the reference does not endorse or certify this tool.