Energy

Electricity Interval Peak Demand & Charge Calculator

Estimate energy and a simple peak-demand charge from equal-duration metered average power intervals.

How the calculation works

Energy = sum(interval kW) × interval hours. Measured peak = maximum interval average. Billed demand = max(measured peak, entered minimum); modeled charges are energy × energy rate plus billed demand × demand rate.

Worked example

Example inputs — Nonnegative interval-average demand (kW): 1, 3, 4, 2; Each billing interval duration (minutes): 15; Energy price per kWh: 0.2; Demand price per kW for period: 10; Minimum billed demand (kW): 0. Expected results — Total metered energy: 2.5 kWh; Highest measured interval demand: 4 kW; Demand used for simple charge: 4 kW; Energy charge: 0.5 your currency; Demand charge: 40 your currency; Combined modeled charges: 40.5 your currency; Load factor over supplied intervals: 62.5 %.

Assumptions and limits

Each sample is average kW over one complete, equal-length utility billing interval. Supply the entire relevant billing period for a period-wide peak; incomplete data may miss it. Uses a single flat energy price, one demand price and an optional minimum demand. No time-of-use, ratchets, coincident peaks, kVA/power-factor charges, taxes, fixed charges, rolling windows or tariff-specific rules are inferred.

Reference and further reading

Read the underlying subject reference. Calculith is an independent implementation; the reference does not endorse or certify this tool.

Related calculators

Browse all 1000 calculators →

Example values are editable. Results are estimates where assumptions apply. Calculations run in your browser. Updated 2026-11-16.