Heat Pump Thermal Balance Point Scenario Calculator

Compare a linear building heat-loss model with a linear interpolation of heat-pump heating capacity at two outdoor temperatures.

How the calculation works

Building load = cold-reference load × (indoor − outdoor)/(indoor − cold reference). Interpolate capacity linearly between the two outdoor references. Solve the intersection of both lines and report it only inside the entered interval.

Worked example

Example inputs — Indoor temperature (°C): 20; Cold reference outdoor temperature (°C): -10; Warm capacity reference outdoor temperature (°C): 10; Building heat loss at cold reference (kW): 9; Heat-pump heat output at cold reference (kW): 6; Heat-pump heat output at warm reference (kW): 6; Outdoor scenario temperature (°C): 0. Expected results — Building heat loss at scenario temperature: 6 kW; Interpolated heat-pump capacity at scenario temperature: 6 kW; Additional heat needed in scenario: 0 kW; Capacity surplus in scenario: 0 kW; Balance temperature within reference interval: 0 °C.

Assumptions and limits

Linear building loss assumes a constant overall heat-loss coefficient and no solar/internal gains. Heating capacities must be measured or manufacturer data at matching operating conditions and include defrost if appropriate. Interpolate only between entered outdoor temperatures; no extrapolation, seasonal energy estimate, COP, backup sizing or design certification. A parallel or coincident line has no unique crossing and is reported as no crossing.

Reference and further reading

Read the underlying subject reference. Calculith is an independent implementation; the reference does not endorse or certify this tool.